- Rectangular mechanical automatic controller
- Factory functional testing of each unit
- No on-site calibration required
- Units are essentially ready for commissioning after installation
Constant volume flow regulators facilitate commissioning in constant systems (CVS). The desired air flow is set at an external scale (RN/EN). There is no other complex or time-consuming calibration.
Even air distribution among the multiple air diffusers only occurs with the appropriate duct layout or after adjustment of the throttle dampers. Volume flow limiters for sliding into the air duct at each diffuser make sense, since both commissioning is easier and quicker and exceeding of the design criteria is prevented.
square, rectangular
40 – 3,360 l/s
144 – 12,096 m³/h
85 – 7,120 cfm
Δp: 50 – 1,000 Pa
W: 200 – 600 mm
H: 100 – 600 mm
circular
11 – 1,400 l/s
40 – 5,040 m³/h
23 – 2,966 cfm
Δp: 50 – 1,000 Pa
Ø 80 – 400 mm
Casing air leakage flow rate complies with DIN EN 1751, class A
circular
11 – 140 l/s
40 – 504 m³/h
23 – 297 cfm
Δp: 50 – 1,000 Pa
Ø 80 – 125 mm
Casing air leakage flow rate complies with DIN EN 1751, class A
circular
4 – 250 l/s
15 – 900 m³/h
8 – 530 cfm
Δp: 30 – 300 Pa
Ø 80 – 250 mm